Programming
ON BOARD DACT
1=RING COUNT

2=CENTRAL STATION

3=MANUAL DIAL MODE
On Board DACT Screen #2
120
3.6.9.2.3.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel
will not answer any incoming calls. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the OnBoard DACT Screen #2. The
following screen will be displayed:
0-25 RANGE
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring
count which can be a value between 00 and 25. After the second digit is entered, the display
will return to the Service Terminal screen.
3.6.9.2.4 Central Station
Central Station programming configures the control panel DACT for contacting the central
station. Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens
to be displayed:
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT
3=CALL LIMIT
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Note that the user will be prevented from entering the Central Station Options Screen while the
DACT is busy calling the Central Station.
3.6.9.2.4.1 Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing
Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will
toggle the display between Reporting Disabled and Reporting Enabled.
RING COUNT
Ring Count Screen
BACKUP
Central Station Screen #1
Central Station Screen #2
0
MS-9050UD PN 52413:C 01/23/08