3.6.11 Clear Program

Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will
cause the LCD to display the following screen:
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general
system programming options and all programmed addressable devices from the nonvolatile
memory of the FACP. This function is useful when the control panel is first installed, prior to
autoprogramming. Note that it is necessary to autoprogram after using the Clear Whole System
function.
See Page
Pressing 2, for ALL POINTS while viewing the Clear Program Screen #1, will clear all
programming related to the SLC loop and connected addressable devices.
Before executing any of the Clear commands listed above, the control panel will provide a warning
to the user by prompting with the following display:
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will
prevent programming from being cleared.
MS-9050UD PN 52413:C 01/23/08
CLEAR PROGRAM
1=WHOLE SYSTEM
2=ALL POINTS
Clear Program Screen #1
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES
Programming
2=NO
135