EDIT MONITOR
1=ENABLED
2=TYPE
MONITOR
Edit Monitor Screen #2
MS-9050UD PN 52413:C 01/23/08
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module
Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No.
If Enabled No is selected, the module will not be polled by the control panel, preventing the
module from reporting alarms and troubles to the panel. The control panel will indicate a
system trouble condition if any devices are disabled.
Type Monitor
Using the PK-CD Upload/Download utility program, unique user-defined monitor types can be
created and loaded into the FACP for later use. The FACP response to the activation of a user-
defined type is the same as most previous standard types in the list, thus allowing a variety of
user-defined types and responses. To select the type of monitor module being programmed,
press the 2 key while viewing the Edit Monitor Screen #2. This will cause the control panel to
display the first Monitor Type Screen as illustrated below
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
To view additional Monitor Type Screens, press the down arrow key. While viewing one of the
Monitor Type screens, select the type of monitor module being programmed by pressing the
corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which
will show the new type selection. The following table lists all of the Monitor Types available
for programming and their respective functions.
MONITOR TYPE
Monitor Type Screen #1
Programming
71