Options Screen - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

If the Parallel Port option is selected, the user has the option to supervise the printer and select
an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print
Options screen #1. Each press of the 2 key will cause the display to toggle between Printer
Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option
is not selectable if the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by
pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer
to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer
supervision is reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be
available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the
Serial Port option has been selected.
Pressing 1 for Baud Rate while viewing ANN-S/PG Options screen #2 will cause a screen to
appear which allow the user to select a Baud Rate of 19200, 9600 or 2400.
Pressing 2 for Data Bits while viewing ANN-S/PG Options screen #2 will cause a screen to
appear which allows the user to select 7 or 8 Data Bits.
Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select between No Parity, Even Parity or Odd Parity.
Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to
appear which allows the user to select between 1.0 or 2.0 Stop Bits.
3.6.9.1.5 ANN-80 Options Screen
Pressing 3 while viewing ANN-BUS screen #2 will display the following screen:
The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options
Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not any installed ANN-80
annunciator must be unlocked by its key before any annunciator key presses will function.
Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock
position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display
to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn
Enable No (Ack/Step button never functions).
MS-9050UD PN 52413:C 01/23/08
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2
Programming
117