User Programming Levels
There are two user programming levels:
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.

3.3 Initial Power-up

The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If
the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and
the following trouble message will be displayed.

3.4 Programming Screens Description

Four options are available when the Enter key is pressed: Read Status, Programming, Manual Dial
Mode and Remote Download. The Read Status and Programming options have multiple functions
or features which may be chosen. To view all of the choices, it is necessary that the programmer
scroll through a number of additional subscreens. These selections are displayed on multiple
screens to make them more readable for the programmer. Refer to "Master Programming Level"
on page 55, for additional information on the various screens.
See Page
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer's convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.

3.5 Programming and Passwords

There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 134. If an invalid password is entered, the blinking cursor will return
See Page
to the first password character position. To exit Programming, Read Status, Manual Dial mode or
Remote Download at any time, press the ESC (Escape) key repeatedly. Note that Programming
mode must be exited using the ESC key in order to store the program data entered during this mode.
If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered
will not be saved.
MS-9050UD PN 52413:C 01/23/08
TROUBL IN SYSTEM
NO DEVICES INSTALLED
09:03A 092105
Programming