Ann-Bus; Ann-Bus Enabled; Modules Installed - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

Programming

3.6.9.1 ANN-BUS

Pressing 1 while viewing the Option Modules screen will cause the control panel to display the
following screens.
A printer module and LCD annunciator module can be programmed into the MS-9050UD
system. These devices communicate with the FACP over the ANN-BUS terminals on the
control panel.

3.6.9.1.1 ANN-BUS Enabled

The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-
BUS Enabled Yes and ANN-BUS Enabled No. The factory default setting is ANN-BUS Enabled
No.

3.6.9.1.2 Modules Installed

If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select
ANN-BUS addresses for the module(s). The following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1-8. To select one or more addresses for the installed module(s), press the number
key corresponding to the module address in each screen. The following screens will be
displayed for each address:
106
ANN-BUS
1=ENABLED
2=MODULES
INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
ANN-BUS Screen #2
ANN-BUS MODULES
1=ADDR. 1
2=ADDR. 2
3=ADDR. 3
ANN-BUS Modules Screen #1
ANN-BUS MODULE
ANN-BUS ADDRESS #
1=TYPE
NO
NONE
NONE
NONE
NONE
MS-9050UD PN 52413:C 01/23/08