Product Description

SECTION 1
The MS-9050UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm
Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent
addressable control panel has an extensive list of powerful features. The combination of Fire-Lite's
newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the
latest in fire protection technology. The power supply and all electronics are contained on a single
circuit board housed in a metal cabinet, providing a complete fire control system for most
applications. Available accessories include local and remote upload/download software, remote
annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PK-CD Upload/Download utility via the public switched telephone
network. Any personal computer with Windows
speed of 2400 baud or faster and Upload/Download software kit PK-CD, may serve as a Service
Terminal. This allows download of the entire program or upload of the entire program, history file,
walktest data and current status.
The MS-9050UDC is a ULC approved Canadian version of the FACP which offers the same
features as the MS-9050UD, but is supplied standard with a dress panel and one built-in ANN-LED
annunciator. Refer to "Canadian Option" on page 102 for a full description.
Note: Unless otherwise specified, the terms FACP and MS-9050UD are used in this manual to refer
to all versions of the FACPs.
Inventory
When the MS-9050UD shipment is received, check to make certain that all parts have been
included in the shipment. The MS-9050UD shipment should consist of one of each of the
following:

1.1 Features and Options

Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
50 addressable device capacity (any combination of addressable detectors and addressable
control/relay/monitor modules totalling 50)
20 software zones
Two onboard NACs (Notification Appliance Circuits) which can be configured as Style Y
(Class B) or Style Z (Class A) circuits
2.5 amps total power for NACs
2.7 amps total system power (includes battery charger)
Two programmable relays and one fixed trouble relay
Built-in Programmer
Telephone Line Active LEDs
Communication Confirmation (Kissoff) LED
Touchtone/Rotary dialing
EIA-232 PC interface for local upload/download
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
12
Product Description
main circuit board with display
chassis with transformer
backbox with door
plastic bag containing screws, cables, key, etc.
manual
XP or newer, and compatible modem with a
MS-9050UD PN 52413:C 01/23/08

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms ms-9050udc

Table of Contents