Product Description
SECTION 1
The MS-9050UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm
Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent
addressable control panel has an extensive list of powerful features. The combination of Fire-Lite's
newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the
latest in fire protection technology. The power supply and all electronics are contained on a single
circuit board housed in a metal cabinet, providing a complete fire control system for most
applications. Available accessories include local and remote upload/download software, remote
annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PK-CD Upload/Download utility via the public switched telephone
network. Any personal computer with Windows
speed of 2400 baud or faster and Upload/Download software kit PK-CD, may serve as a Service
Terminal. This allows download of the entire program or upload of the entire program, history file,
walktest data and current status.
The MS-9050UDC is a ULC approved Canadian version of the FACP which offers the same
features as the MS-9050UD, but is supplied standard with a dress panel and one built-in ANN-LED
annunciator. Refer to "Canadian Option" on page 102 for a full description.
Note: Unless otherwise specified, the terms FACP and MS-9050UD are used in this manual to refer
to all versions of the FACPs.
Inventory
When the MS-9050UD shipment is received, check to make certain that all parts have been
included in the shipment. The MS-9050UD shipment should consist of one of each of the
following:
1.1 Features and Options
•
Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download
•
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
•
50 addressable device capacity (any combination of addressable detectors and addressable
control/relay/monitor modules totalling 50)
•
20 software zones
•
Two onboard NACs (Notification Appliance Circuits) which can be configured as Style Y
(Class B) or Style Z (Class A) circuits
•
2.5 amps total power for NACs
•
2.7 amps total system power (includes battery charger)
•
Two programmable relays and one fixed trouble relay
•
Built-in Programmer
•
Telephone Line Active LEDs
•
Communication Confirmation (Kissoff) LED
•
Touchtone/Rotary dialing
•
EIA-232 PC interface for local upload/download
•
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
12
Product Description
main circuit board with display
chassis with transformer
backbox with door
plastic bag containing screws, cables, key, etc.
manual
™
XP or newer, and compatible modem with a
MS-9050UD PN 52413:C 01/23/08