Edit Module Screen For Control Modules - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
MS-9050UD PN 52413:C 01/23/08
As an example, the user could quickly enter 'FLR_3_ROOM 305' as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the Enter key to store the information

3.6.2.2.4 Edit Module Screen for Control Modules

The programmer can change a module's existing or factory default programming by pressing 3
in the Modules Screen. The following screen will be displayed:
ENTER MODULE ADDRESS
***
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is
keyed-in, if the selected address corresponds to a control module, a screen displaying
information about the control module with the selected address will be displayed as illustrated
in the following:
NORMAL
In the preceding example:
Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device
Control - indicates that the selected module is a control module
S or * - represents Silenceable (S) or Nonsilenceable (*)
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 019)
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module
and 002 = Module Address 02)
EDIT MODULE
Edit Module Screen
CONTROL
<ADJ><NOUN>
ZNNN
SW
1M002
Edit Control Screen #1
Programming
77