Honeywell Fire-Lite Alarms MS-9050UD Manual page 49

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

Before installing the module, place the disconnect switch to the right (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the MS-9050UD. In addition, the System Trouble LED will turn on
to indicate the Disconnect condition.
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application using reverse polarity of a supervisory
signal, refer to "FACP with Keltron" on page 195.
MS-9050UD PN 52413:C 01/23/08
+
- +
-
+
-
1
2
3
4 5
6
7
TBL Jumper
Figure 2.10 4XTMF Transmitter Module
}
Remote Alarm (power-limited)*
}
Remote Trouble (power-limited)*
No connection
}
Municipal Box (nonpower-limited)*
Polarities are shown for module activation
Connect to FACP J8 & J9
Installation
* Wiring from these
terminals can exit the
protected premises.
Dummy load terminals
6 and 7 (4.7kΩ, ¼ watt
resistor) if Municipal
Box is not connected.
Disconnect LED
Disconnect Switch
shown in disconnect
position
49