Transferring A Program - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

The Remote Download password (default 00000) must be entered to access the Remote Download
feature. Note that the default password can be changed using the Password Change option (refer to
"Password Change" on page 134). Entering the correct password will cause the following screen to
be displayed:
Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download
screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the
1 key will cause the display to toggle between Proprietary No and Proprietary Yes. Selecting
Proprietary Yes will program the FACP to allow remote programming downloads from the PK-Plus
programming utility at all times without the need to access the Remote Download screen.
Pressing 2 for Accept Download will cause the following screen to be displayed:
While this screen is displayed, remote programming downloads are allowed regardless of the
Proprietary setting. Exiting this screen will disable any further downloads to the FACP. Also,
following 30 minutes of inactivity (including up/downloading), the Accept Download screen will
time-out, causing the display to return to the System All Normal screen.

6.2 Transferring a Program

The first time that the control panel is contacted, a secret code is loaded in by a Service Terminal.
Future upload or download requests cause verification of the secret code by the control panel
before processing of data is allowed. If the secret code is not verified, the control panel will
terminate the request.
While the control panel is communicating with the remote Service Terminal, one of the DACT's
red phone line active LEDs and the green Kissoff LED will remain on steady. These LEDs do not
light for local (direct connect) programming.
In order to download to the panel, the following must be true:
The control panel must be in the Normal Mode of operation. Downloading is not allowed
if the panel is in any other mode
There cannot be any active communications ongoing with a Central Station receiver
All active events must be successfully 'kissed-off' by the Central Station(s). The
communicator must be in a standby state with no new information waiting to be
transmitted to a Central Station
MS-9050UD PN 52413:C 01/23/08
REMOTE DOWNLOAD
1=PROPRIETARY
2=ACCEPT DOWNLOAD
*ALLOWING DOWNLOADS*
IF YOU EXIT THIS
SCREEN DOWNLOADS
WILL BE DISABLED!
Local/Remote Site Upload/Download
NO
177