Specifications - Honeywell Fire-Lite Alarms MS-9050UD Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

History file with 500 event capacity
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) per addressable detector and Pre-signal per point (NFPA 72
compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with
two-stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote
annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same
address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
SLC operates up to 10,000 ft. (3,000 m) with twisted, unshielded fire wire
Compatible with Fire-Lite addressable devices (refer to SLC Wiring Manual)
Compatible with legacy Fire-Lite 300 Series addressable devices (refer to SLC Wiring
Manual)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional ANN-I/O LED Driver module
Optional ANN-S/PG printer interface module
Optional ANN-80 remote LCD annunciator
Optional ANN-LED Annunciator Module annunciates alarm, trouble and supervisory
Optional ANN-RLED Annunciator Module annunciates alarms only
Optional ANN-RLY Form-C Relay Module
Optional Dress Panel DP-51050 (a modified dress panel is included standard with the
MS-9050UDC)
Optional PRN-6F Serial Printer (requires ANN-S/PG module)

1.2 Specifications

Refer to Illustration on page 10 for terminal locations and connections.
For wire specifications, refer to "Wire Requirements" on page 196.
AC Power - Transformer Connection
MS-9050UD: 120 VAC, 60 Hz, 3.0 amps
Wire size: minimum 14 AWG (2.00 mm
Nonpower-limited, supervised
MS-9050UD PN 52413:C 01/23/08
2
) with 600 V insulation
Product Description
13