Honeywell Fire-Lite Alarms MS-9050UD Manual page 62

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9050UD:
Table of Contents

Advertisement

Programming
See Page
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
See Page
62
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time
of up to 3 minutes. Zone 17, however, will activate immediately and may be used to connect a
signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this
purpose). To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until
the display reads PAS Yes. Each press of the 2 key will cause the display to toggle between PAS
Yes and PAS No. Refer to "Positive Alarm Sequence" on page 156.
For example, if a detector with address 005 is to be configured for PAS operation:
Select PAS Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
Program an output, such as a control module, for PAS activation by assigning zone Z17 to
it. This control module may be connected to a signaling device used to indicate a PAS
condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 17 and set the PAS delay timer to some
value
With the preceding program settings, when the detector with address 005 is activated, zone Z17
will cause its associated control module to activate immediately, sounding the connected PAS
signaling device. Following the PAS delay time, zone Z001 will cause its associated control
module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the
alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone
18 will activate. This zone can be programmed to a control module which may be used to
activate a sounder or indicator which the installer designates as a Presignal indication (do not
use a Notification Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3
while viewing Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the
3 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to
"Presignal" on page 155.
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
Select Pre-signal Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
Program an output, such as a control module, for Pre-signal activation by assigning zone
Z18 to it. This control module may be connected to a signaling device used to indicate a
Pre-signal condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 18 and set the Pre-signal delay
timer to some value
MS-9050UD PN 52413:C 01/23/08