Pressing 1 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number
(00 - 19). After the second digit is entered, the zone will be enabled and the cursor will return to the
original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to
the previous screen.
Pressing 2 while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To disable a zone, enter the two digit zone number
(00 - 19). After the second digit is entered, the zone will be disabled and the cursor will return to
the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to
return to the previous screen.
Pressing 3 while viewing Zone Setup screen will display the following screen:
Zones 17, 18 and 19 can be programmed for normal zone operation or for special purpose
applications. In the above illustration, the three zones are shown Off, which means they can be
programmed to function in the same manner as all other zones, by assigning them to input and
output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the
display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By
assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to
indicate a PAS condition.
MS-9050UD PN 52413:C 01/23/08
ZONE TO ENABLE
Z
Enable Screen
ZONE TO DISABLE
Z
Disable Screen
SPEC PURPOSE ZONE
1=PAS 17
2=PRE-SIGNAL 18
3=TWO STAGE 19
Disable Screen
Programming
OFF
OFF
OFF
145