3.6.5 System Setup

System Setup allows the programmer to configure the following control panel features:
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
MS-9050UD PN 52413:C 01/23/08
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared.
Trouble Resound is independent of Trouble Reminder. If a silenced trouble condition is not
cleared by midnight, the panel will reactivate the trouble sounder.
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout to a user defined readout when the control panel is in Normal
condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 102).
Important! For Canadian Applications, this option must be set to ON prior to any other
panel programming.
Waterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.
1=TROUBLE REM
2=BANNER
3=TIME-DATE
1=TIMERS
2=NAC
3=RELAYS
1=CANADIAN OPT.
2=WATERFLOW SIL.
SYSTEM SETUP
System Setup Screen #1
SYSTEM SETUP
System Setup Screen #2
SYSTEM SETUP
System Setup Screen #3
Programming
OFF
OFF
NO
89

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms ms-9050udc

Table of Contents