Programming

3.6.8 Walktest

Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Pressing 2 while viewing the Programming Screen #3 will cause
the following Walktest options to be displayed:
PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:
From this screen, it is possible to view the walktest log, untested system points or a summary of the
addressable devices tested during the current walktest. The user can select between any of these
screens without interrupting the current walktest session. The walktest session will not end until
the Unit In Walktest screen is exited by pressing the Escape key.
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen
similar to one of the following two screens to be displayed:
NO EVENTS IN
WALKTEST LOG
If there are no events in the current walktest session, the first screen will be displayed, indicating no
events have been stored in the walktest log. If any events have been stored, a screen similar to the
second will be displayed indicating the latest event. As walktest events occur, the display will
change to indicate the latest event. All stored events can be scrolled on the screen by pressing the
up or down arrow keys. To return to the first event, press the 1st Event key.
Pressing 2 for View Points while viewing the Unit In Walktest screen will display a new screen
which will show only the points that have not yet been walk tested. The up and down arrow keys
will allow viewing of all untested points. If a point is tested while it is being displayed, the screen
will update and display the next untested point. A description on the bottom of the screen will
indicate if the displayed point has been disabled, if the Walktest option has been disabled for that
point or if the point is not yet tested. The total number of untested points can be seen in the upper
right corner of the screen.
104
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
Unit In Walktest Screen
ALARM: MONITOR
NORTH CLASSROOM
OR
10*15A 012308 1M006
Z001
MS-9050UD PN 52413:C 01/23/08