Programming
ANN-LED Point Option - Alarm, Trouble and Supervisory
If Point is selected as the module option, and the module is programmed to annunciate alarms,
troubles and supervisories, the first ten LEDs on the first ANN-LED module will display the
system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on
the remaining modules will display the alarm, trouble and supervisory status for each of the ten
points in the Point Range programmed for that particular module. The LED assignments for
each ANN-LED module will be as follows.
Alarm Silenced
Earth Fault
Point 01
Active/Alarm
Point 01
Trouble
Point 01
Supervisory
Point 06
Active/Alarm
Point 06
Trouble
Point 06
Supervisory
Not Used
Not Used
Point 11
Active/Alarm
Point 11
Trouble
Point 11
Supervisory
Point 16
Active/Alarm
Point 16
Trouble
Point 16
Supervisory
The LED assignments for the modules annunciating Point Ranges 21 - 30, 31 - 40 and 41 - 50,
will follow the same pattern as the second ANN-LED Module.
114
First ANN-LED Module (Point Range 01 - 10)
NAC 1 Fault
NAC 2 Fault
Battery Fault
Charger Fault
Point 02
Point 03
Active/Alarm
Active/Alarm
Point 02
Point 03
Trouble
Trouble
Point 02
Point 03
Supervisory
Supervisory
Point 07
Point 08
Active/Alarm
Active/Alarm
Point 07
Point 08
Trouble
Trouble
Point 07
Point 08
Supervisory
Supervisory
Second ANN-LED Module (Point Range 11 - 20)
Not Used
Not Used
Not Used
Not Used
Point 12
Point 13
Active/Alarm
Active/Alarm
Point 12
Point 13
Trouble
Trouble
Point 12
Point 13
Supervisory
Supervisory
Point 17
Point 18
Active/Alarm
Active/Alarm
Point 17
Point 18
Trouble
Trouble
Point 17
Point 18
Supervisory
Supervisory
Not Used
Not Used
Disabled
Maintenance
Point 04
Point 05
Active/Alarm
Active/Alarm
Point 04
Point 05
Trouble
Trouble
Point 04
Point 05
Supervisory
Supervisory
Point 09
Point 10
Active/Alarm
Active/Alarm
Point 09
Point 10
Trouble
Trouble
Point 09
Point 10
Supervisory
Supervisory
Not Used
Not Used
Not Used
Not Used
Point 14
Point 15
Active/Alarm
Active/Alarm
Point 14
Point 15
Trouble
Trouble
Point 14
Point 15
Supervisory
Supervisory
Point 19
Point 20
Active/Alarm
Active/Alarm
Point 19
Point 20
Trouble
Trouble
Point 19
Point 20
Supervisory
Supervisory