4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
•
The piezo sounder pulses ¼ second On and ¼ second Off
•
The LCD displays a process monitor message along with the device name, type, address,
adjective/noun, associated zones and time/date
•
Communicate the process monitor condition to the Central Station
•
Relays programmed for process monitoring will be activated
•
The alarm relay is not activated
•
NACs will not activate
•
Timers are not started
•
Store event in history buffer
Note that, like supervisories, process monitor signals latch (except when programmed for process
monitor autoresettable) and can be assigned to software zones.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado Condition operation will initiate the following events:
•
The piezo sounder pulses ½ second On, ½ second Off
•
The LCD displays a hazard message along with the device name, type, address, adjective/
noun, associated zones and time/date
•
Communicate the hazard condition to the Central Station
•
Relays programmed for hazard will be activated
•
The alarm relay is not activated
•
NACs will not activate
•
Timers are not started
•
Store event in history buffer
•
Supervisory LED flashes ½ second On, ½ second Off
Hazard conditions latch. They can be assigned to software zones.
4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
•
The piezo sounder ½ second On, ½ second Off
•
The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones and time/date
•
Communicate the medical alert condition to the Central Station
•
Relays programmed for medical alert will be activated
•
The alarm relay is not activated
•
NACs will not activate
•
Timers are not started
•
Store event in history buffer
•
Supervisory LED flashes ½ second On, ½ second Off
Medical alert conditions latch. They can be assigned to software zones.
4.10 NAC Operation
There are two programmable NACs (Notification Appliance Circuits) resident on the MS-9050UD
main circuit board which can be wired for Style Y (Class B) or Style Z (Class A) . Both NACs may
be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded
operation. Coded operation provides a choice between March Time, Temporal or California
coding.