Installing Pipes - Huawei FusionCol8000-E400 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
● Install air filters by referring to the direction instruction on the frame to ensure
correct installation.
● Ensure that the pressure inlet tube of the differential pressure switch is not
blocked or bent. Insert the pressure inlet tube between the air filter and the
heat exchanger core, but not into the heat exchanger core.
Step 8 Close all the maintenance doors.
----End

4.4 Installing Pipes

Pipe Installation
● Clean the external water pipes before connecting them to the water inlet and
outlet pipes of the coil pipes of the unit.
● Water pipes need to be prepared onsite.
● Connect the water inlet and outlet pipes of the unit using pipe thread
connectors. When connecting the water pipes, do not exert excessive force to
avoid damage to the coil pipes. (When connecting the pipes, use two pipe
wrenches or chain pliers.)
● After installing water pipes, install supports to secure the pipes.
● The drainpipe should have a downward gradient of at least 5‰ in the drainage
direction to ensure smooth drainage.
Issue 04 (2022-06-30)
NO TICE
NO TICE
Copyright © Huawei Technologies Co., Ltd.
4 System Installation
49