Installing The Equipment; Unpacking And Checking - Huawei FusionCol8000-E400 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Table 4-3 Cables
Item
Power cable
Air damper cable
(Optional) T/H
sensor cable, water
sensor (rope type),
and teamwork and
monitoring
communications
cables
Equipotential
ground lug/ground
cable

4.3 Installing the Equipment

4.3.1 Unpacking and Checking

Context
Move the unit closest to the installation position before unpacking it to facilitate
movement and avoid damage.
Procedure
Step 1 Check that the external package of the unit is intact. If any damage is found,
notify the carrier immediately.
Step 2 Check whether the exterior of the unit is in good condition and free of collision
marks or scratches. If any damage is found, notify the carrier immediately.
Issue 04 (2022-06-30)
Recommended Specifications
Active power input: 3 x 120 mm
(PE)
Standby power input: 3 x 120 mm
(PE)
4 x 0.75 mm
CAT 5e or higher shielded network cable
● Ground lug: Use hot-dip zinc-coated flat steel sheet
● Ground cable: Use equipotential ground cables with a
NO TE
During movement, do not tilt it for 90
Copyright © Huawei Technologies Co., Ltd.
2
with a cross-sectional area greater than or equal to 50
2
mm
.
cross-sectional area of at least 16 mm
ground cables through a plastic-coated metal hose.
°
.
4 System Installation
2
(L1/L2/L3) + 70 mm
2
(L1/L2/L3) + 70 mm
2
and route the
2
2
37