● The default T/H sensor address is 1.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
● If the T/H sensor provided is black and has an LCD, bits 1 to 6 of the DIP switch
are used to set the device address, bit 7 is reserved, and bit 8 is used to switch
the temperature display mode.
----End

4.6 (Optional) Installing a Rainproof Canopy

Procedure
Step 1 Assemble the rainproof canopies 1# to 4#.
Step 2 Attach rubber strips to the frame of the screws securing the unit in the sequence
from 1# to 2#, and then secure rainproof canopies 1# and 2# using nine M10x25
screws, as shown by (1) in
Step 3 Install the water-retaining sheet metals under the rainproof canopies 1# and 2#.
Step 4 Attach rubber strips to the frame of the screws securing the unit in the sequence
from 3# to 4#, and then secure rainproof canopies 3# and 4# using nine M10x25
screws, as shown by (1) in
Step 5 Use six M10x25 screws to secure the 3# and 4# rainproof canopies to the beam
above the outdoor air intake vent, as shown by (2) in