Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the No. 3 maintenance door and find the compressor to be maintained.
Step 3 Reclaim the refrigerant from the low pressure needle valve and discharge pipe
needle valve to ensure that there is no pressure inside the system.
Step 4 Remove the electric heating belt.
Step 5 Remove the cover of the connection box and disconnect the compressor power
cables.
Step 6 Remove the compressor.
1.
Issue 04 (2022-06-30)
NO TICE
Use a welding torch to separate the welding points for the suction and
discharge pipes from the compressor. After the separation, seal the discharge
vent immediately.
Figure 9-11 Removing a compressor