3.3.5 Installing Water Pipes

Installing Water Pipes
● Ensure that the external pipes are clean and free from foreign matter before
connecting to the water inlet and outlet pipes. Do not let external impurities
enter the pipes.
● The water inlet and outlet pipes of the unit are connected using screw threads.
Do not exert excessive force when connecting the pipes to avoid damaging the
pipes. (Use two pipe pliers or chain pliers to connect pipes.)
Take out the water seal from the fittings bag and install it in the correct position.
After water pipes are installed, wrap thermal insulation foam.
Water inlet pipes need to be prepared onsite. If galvanized steel pipes are used,
stainless steel connectors must be used to ensure sealing.
Figure 3-11 Water inlet and outlet pipes
(1) Water tank refill pipe
(3) Condensate water pan drainpipe of the
evaporator
● When installing the water seal, keep it horizontal and allow a maximum
downward inclination of 5°.
● When installing the water seal, strictly follow the installation diagram (as
shown in
Issue 01 (2021-01-30)
NO TICE
NO TICE
Figure
3-11) to avoid reverse connection of the water seal.
Copyright © Huawei Technologies Co., Ltd.
3 System Installation (Building Scenario)
(2) Water tank drainpipe
(4) Condensate water pan drainpipe