Procedure
Step 1 On the home screen, choose Settings > Comm Settings > WAN IP Settings, and
set the IP address, subnet mask, and gateway based on the actual plan.
Figure 6-5 WAN IP Settings
Step 2 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Parameter
Link mode
Client encryption
Server encryption
Encryption algorithm
CBC
NMS IP address
Issue 04 (2022-06-30)
NO TE
The WAN IP address cannot be in the 192.168.245.X, 192.168.246.X, or 192.168.248.X
network segment.
Copyright © Huawei Technologies Co., Ltd.
Description
● Server: The smart cooling product works as the
server and can connect to two clients for
communication.
● Client: The smart cooling product works as the
client and can connect to a remote server for
communication.
● Server and client: The smart cooling product works
as the server and can connect to two clients for
communication. It also works as the client and can
connect to a remote server for communication.
This parameter is configurable when Link mode
involves Client.
This parameter is configurable when Link mode
involves Server.
Specifies whether to use the CBC encryption algorithm.
After the parameter setting is changed, the system
automatically restarts. Exercise caution with the setting.
Enter the actual IP address of the NMS. The IP
addresses of the display board, client NMS, and server
NMS must be unique.
This parameter is configurable when Link mode
involves Client.
6 Power-On and Commissioning