Huawei FusionCol8000-E400 User Manual page 85

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Tab
Issue 04 (2022-06-30)
Parameter
DO_1
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Description
● If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or
water overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_1 acts according to
DO_1 action when a critical alarm
is generated.
● If this parameter is set to Major
alarm, DO_1 acts according to
DO_1 action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_1 acts according to DO_1
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_1 acts according to
DO_1 action when the unit is
started.
● If this parameter is set to No, no
alarm is generated when DO_1 is
disconnected.
77