Replacing A Compressor Drive - Huawei FusionCol8000-E400 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Charge refrigerant on the basis of the precharging.
Step 5 On the home screen, choose Running > Device Details > Compressor, and view
Suction pressure and Discharge pressure to determine whether they are within
normal ranges. Choose Running > Device Details > EEV and view EEV suction
superheat degree to determine whether it is within the normal range.
Table 9-3 Proper discharge pressure range
Outdoor
Ambient
Temperature
< 15°C
15–35°C
35–45°C
> 45°C
If the suction pressure, discharge pressure, and suction superheat degree are not within the
normal range, check the following items:
1. Refrigerant is charged to the standard amount. (If the refrigerant is overfilled, the discharge
pressure will be high. If the refrigerant is underfilled, the suction and discharge pressures will
be low, and the suction superheat degree will be high.)
2. The air intake vent and air exhaust vent of the outdoor unit are not blocked. (If the air
intake vent and air exhaust vent are blocked, the discharge pressure will be high.)
Step 6 After charging refrigerant, close all valves.
Step 7 Tap
Step 8 Tap Shutdown on the home screen.
----End

9.7 Replacing a Compressor Drive

Prerequisites
Issue 04 (2022-06-30)
NO TICE
Discharge
Pressure Range
1.5–2.5 MPa
1.5–3.1 MPa
2.5–3.8 MPa
3.1–4.15 MPa
NO TE
to exit the diagnostic mode.
A drive needs to be replaced.
A spare drive of the same model is available and functional.
Tools: Phillips screwdriver, diagonal pliers, cable tie
Copyright © Huawei Technologies Co., Ltd.
9 Parts Replacement
Suction Pressure
Suction
Range
Superheat
Degree
0.7–1.2 MPa
8–15°C
142