Step 2 You can tap an alarm to go to the Details screen of the alarm.
Figure 10-11 Alarm details
Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults by
following instructions in the diagnosis report.
----End
Follow-up Procedure
To query historical alarms, choose Common Function > Query Hist Alarms on
the home screen or choose Alarms > Query Hist Alarms on the home screen.

10.2.10 How Do I Clear Component Runtime?

Context
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken the
performance of the unit.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End

10.2.11 How Do I Calibrate a T/H Sensor?

Context
Calibrate a sensor if the displayed temperature or humidity values on the sensor
deviate from the actual values. For example, if the return air temperature