FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Item
Foundatio
n
Water
supply
Power
distributio
n
Note: If the requirements are not met, contact technical support for an
optimized solution.
Issue 04 (2022-06-30)
Specifications
Bearing capacity of each support point: > 1850 kg (six support
points)
Equivalent uniformly distributed load: ≥ 550 kg/m
● It is recommended that a water pressure gauge and a manual
ball valve be installed on the external water refill pipe of the
unit so that the water supply pressure can be easily adjusted
and the water refill pipe can be maintained individually for the
unit.
● The water supply pressure must range from 0.1 MPa to 0.7
MPa.
● Water quality requirements:
– Turbidity ≤ 5 NTU
– 6.5 ≤ PH (25°C) ≤ 8.5
– Conductivity < 600 μS/cm
CAUTION
If the quality of tap water onsite does not meet the requirements,
reduce the concentration times. Drain the water if the conductivity of
circulating water in the water tank of the unit exceeds 1800 μS/cm.
– Total hardness ≤ 100 mg/L
– Total alkalinity ≤ 200 mg/L
– Chlorine ion ≤ 150 mg/L
– COD ≤ 30 mg/L
Leakage circuit breakers are not recommended for the main power
supply route. If a leakage circuit breaker is required by the
customer or local regulations, select the residual current circuit
breaker (RCCB) that is insensitive to single-phase DC pulsation and
transient impulse current.