Can Teamwork + Fe Monitoring - Huawei FusionCol8000-E400 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Figure 4-28 Connecting communications cables
----End

4.5.5.2.2 CAN Teamwork + FE Monitoring

Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Description
Issue 04 (2022-06-30)
NO TE
● Connect the COM/FE port on the main control module of the last unit in each group to
the RS485 port on the host.
● Customers can purchase an ECC and NetEco as the monitoring system.
CAN Teamwork
CAN
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
NO TE
Customers can purchase a switch and NetEco as the monitoring system.
Copyright © Huawei Technologies Co., Ltd.
4 System Installation
FE Monitoring
Modbus-TCP/SNMP
-
60

Advertisement

Table of Contents
loading

Table of Contents