Huawei FusionCol8000-E400 User Manual page 99

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Figure 6-9 Teamwork Settings
Step 2 Set teamwork parameters.
All teamwork control parameters can be set on the master unit. Only Teamwork
group No., System address, Enable teamwork CAN resistor, Teamwork
function, and Networking mode can be set on slave units. Other parameters of
the slave units will be modified by the master unit synchronously.
Parameter
Teamwork group No.
System address
Networking mode
Enable teamwork CAN
resistor
Teamwork function
Issue 04 (2022-06-30)
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality
will be affected, and even the teamwork CAN
networking will fail.
Yes: The teamwork control CAN resistor is enabled
for the unit.
No: The teamwork control CAN resistor is disabled
for the unit.
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Copyright © Huawei Technologies Co., Ltd.