FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Item
Storage
humidity
IP rating
Installatio
n mode
Altitude
1
If servers are not evenly deployed or the difference between the intake and
exhaust air temperatures of the servers is less than 10°C, the cooling capacity of
the unit will decrease and its power will increase.
Table 3-4 Derating coefficients
Altitude
(m)
Air volume
coefficient
Cooling
capacity
coefficient
Installation Requirements
If the total actual load of servers for each equipment is less than 10% of the rated
cooling capacity or the equipment room is not properly sealed, the humidity in the
equipment room may exceed the upper limit, which is not a product quality issue
and should be dealt with by adding a dehumidifier.
Table 3-5 Installation requirements
Item
Transporta
tion
passage
Issue 04 (2022-06-30)
Specifications
5%–95% RH
IPX5 (indoor)
Concrete foundation required
The device can work properly at an altitude below 1000 m, and
derating is allowed. For details about derating, see the following
table.
1000
1500
0.887
0.835
0.887
0.835
NO TICE
Specifications
Width > 4500 mm; height > 4500 mm
Copyright © Huawei Technologies Co., Ltd.
2000
2500
3000
0.785
0.737
0.692
0.785
0.737
0.692
3 Product Specifications
3500
4000
0.649
0.608
0.649
0.608
28