Huawei FusionCol8000-E400 User Manual page 174

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Figure 10-12 Pressure tube positions
(1) Sheet metal for installing the condensate
drainpipe
(3) Position for the negative pressure tube
Step 7 Remove the pressure tubes and seal the air duct holes.
Step 8 Tap Start on the home screen. Ensure that the device is running normally without
any alarms.
Step 9 Log in to the WebUI as user admin, choose Settings > System Settings > System
Control > Advanced, and set Static pressure.
Step 10 Choose Running > Status Summary and view the value of air volume.
Issue 04 (2022-06-30)
NO TE
● If the distance is not 4.5 m, adjust it to be close to 4.5 m.
● Choose Maint > Diagnostic Mode > Enter and set the indoor fan speed to the
maximum value.
Copyright © Huawei Technologies Co., Ltd.
(2) Negative pressure tube
(4) Hole for the positive static pressure
10 FAQ
166