NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Step 2 You can tap an alarm to go to the Details screen of the alarm.
Figure 12-16 Alarm details
Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults by
following instructions in the diagnosis report.
----End
Follow-up Procedure
To query historical alarms, choose Common Function > Historical Alarms on the
home screen or choose Alarms > Historical Alarms on the home screen.

12.3.11 How Do I Clear Component Runtime?

Context
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken the
performance of the unit.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End
Issue 04 (2022-12-15)
NO TE
● Active alarms are displayed by generation time. The latest generated alarm is displayed
in the uppermost row.
● If active alarms exist, they are displayed on the alarm bar in turn.
● You can query an alarm on the alarm list in "Alarm Reference" based on the alarm ID to
know causes of the alarm and methods to clear the alarm.
NO TE
Historical alarms are displayed in chronological order. The latest cleared alarm is displayed
in the uppermost row.
NO TICE