Step 5 Perform a leakage test with nitrogen.
Step 6 After checking that the smart cooling product does not leak, vacuumize the smart
cooling product and fill the refrigerant.
Step 7 Power on the device and tap Start on the home screen. Ensure that the smart
cooling product is running normally without any alarms.
----End
8.4.15 Replacing a Compressor Drive
Prerequisites
●
●
●
Context
Before checking and maintaining the device, ensure that the primary power supply
to the device is disconnected and the drive has been powered off for 10 minutes.
Otherwise, electrical shocks may occur.
Procedure
Step 1 On the controller home screen, tap Shutdown and turn off the device switch in
the PDF.
Issue 01 (2021-01-30)
Figure 8-28 Installing the filter dryer
A drive needs to be replaced.
A spare drive of the same model is available and functional.
Tools: Phillips screwdriver, diagonal pliers, cable tie
NO TICE
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
171