6 DATA USED FOR POSITIONING CONTROL
6.2.3 Exchange of the servo parameters
FROM(P) instruction, DFRO(P) instruction
MOV(P) instruction, DMOV(P) instruction
QD74MH
Internal memory
Parameter
This section describes the exchange of the servo parameters.
(1) Writing the servo parameters from QD74MH to servo amplifier
Some servo parameters become valid by turning OFF/ON of the power supply of
the servo amplifiers. (Refer to Section 6.8.)
Change procedure is shown below.
1) Change the servo parameters and write them to the buffer memory.
2) Execute the flash ROM write.
3) (Change the parameters after procedure 3), if not required.)
4) Turn the power supply ON of the servo amplifiers.
5) Turn the PLC READY ON. (The parameters changed can be transmitted to
the servo amplifiers.)
6) Turn the power supply OFF of the system and the servo amplifiers.
7) Turn the power supply ON of the system and the servo amplifiers.
(The parameters changed become valid.)
8) Turn the PLC READY ON.
PLC READY ON
Servo parameter change
PLC CPU
1)
TO(P) instruction, DTO(P) instruction
MOV(P) instruction, DMOV(P) instruction
3), 7)
Buffer memory
System power supply ON/
Reset of the PLC CPU
Parameter
Positioning data
Servo parameter
2)
"1" is set in "
Monitor data
ROM write request".
Control data
Interface for
communication with
servo amplifier
5), 8)
Communication start with servo amplifier
(PLC READY ON (First time only))
Servo amplifier
4), 6), 7)
6 - 6
MELSEC-Q
Flash ROM
Parameter
Positioning data
Servo parameter
Flash
Cd.100