Mitsubishi Electric MELSEC Q Series User Manual page 104

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

6 DATA USED FOR POSITIONING CONTROL
Buffer
memory
Symbol
address
Pr.25
25+100n Interpolation group
26+100n
Linear interpolation
Pr.26
27+100n
speed limit value
External input signal
Pr.31
31+100n
logic selection
Items
Set the group to specify the
combination for axes to be
interpolation-controlled.
Set the same group number for
axes to be interpolation-controlled.
• Up to 4 axes can be set to one
group.
• Up to 4 groups can be set.
Set the maximum speed at the
linear interpolation control.
Select the logic of the external
input signal.
b15
to
b12
b11
0
0
0
0
0
b8: Proximity dog
b4: Lower hardware
strok limit
b0: Upper hardware
strok limit
(Note): Set to "0" for except the
above bits.
Details
Setting range
0: None
(Single axis)
1: Group 1
2: Group 2
3: Group 3
4: Group 4
1 to 2147
to
b8
b7
to
b4
b3
to
b0
0
0
0
0
0
0
0
0
0
0
0
0: Negative logic
1: Positive logic
6 - 25
MELSEC-Q
Factory
Fetch timing
default
PLC READY ON
0
PLC READY ON/
Parameter
10
change request
PLC READY ON
0
Unit
6
×10
[PLS/s]

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qd74mh