9 MANUAL CONTROL
BUSY signal [X10 to X1F]
BUSY signal [X10 to X1F] OFF
BUSY signal [X10 to X1F]
BUSY signal [X10 to X1F] OFF
(1) When "1" is set in both the forward rotation JOG start and reverse
rotation JOG start simultaneously
When "1" is set in both "
rotation JOG start" simultaneously for one axis, the "forward rotation JOG start"
is given priority. In this case, the reverse rotation JOG start signal is validated
when the forward rotation JOG operation is stopped.
Forward rotation
Cd.8
JOG start
Reverse rotation
Cd.9
JOG start
(2) When "1" is set again in JOG start during deceleration caused by
changing from "1" to "0" of JOG start setting
When "1" is set again in JOG start for same direction during deceleration caused
by changing from "1" to "0" of JOG start setting, the acceleration and JOG
operation are executed without wating for the stop.
Forward rotation
Cd.8
JOG start
Forward rotation JOG start" and "
Cd.8
Forward rotation
JOG operation
0
1
Reverse rotation JOG
start signal is ignored.
0
ON
Forward rotation JOG operation
0
1
ON
9 - 3
MELSEC-Q
Cd.9
Reverse rotation
JOG operation
0
1
0
1
Reverse
0
0