FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)
Category
Item
Overload capability
Battery
Charge voltage
parameter
System
System capacity
parameter
Number of configured
power modules
Cable connection
Noise
Others
Maintenance mode
Surge protection
3.2.3 rPDU
The figure is for reference only. The actual product prevails.
Figure 3-20 Full height rPDU
Table 3-6
Table 3-6 rPDU specifications
Model
PDU2000-40-2PH-20/2-B1
Issue 03 (2021-02-10)
NO TE
lists the rPDU specifications.
Copyright © Huawei Technologies Co., Ltd.
Specifications
Inverter overload capability:
● 100% < load ≤ 110%: transfer to bypass mode
after 60 minutes
● 110% < load ≤ 125%: transfer to bypass mode
after 10 minutes
● 125% < load ≤ 150%: transfer to bypass mode
after 1 minute
Equalized charging voltage: 2.35 V/cell; float
charging voltage: 2.25 V/cell
60 kVA
3
Routed in and out from the top
At atmospheric pressure (25°C)
● 25% load: 54 dB
● 50% load: 58 dB
● 75% load: 61 dB
● 100% load: 65 dB
Maintained from the front or rear
Level C SPD
Output Connector
IEC320 20 x C13 + 2 x C19
3 Architecture
25