Quarterly Maintenance; Annual Maintenance - Huawei PDU8000 User Manual

Modular precision pdc
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)

8.2.2 Quarterly Maintenance

Table 8-3 Quarterly Maintenance
Maintenance
Item
PDC component
appearance
Operating
temperature and
humidity of the
PDC

8.2.3 Annual Maintenance

Table 8-4 Annual Maintenance
Maintenance
Item
PDC interior
Oxidation of
metal components
in the PDC
Issue 02 (2017-02-24)
Operation
Guide
Visual
observation
Point
thermometer
Operation
Guide
Check whether
dust has
accumulated on
the PDC
mounting panels.
Visual
observation
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Expected
Exception Handling
Result
The exterior is
Take measures depending on
intact.
the severity.
Operating
Check whether the air
temperatur
conditioner and dehumidifier in
e: –10° C to
the equipment room function
+55° C
properly.
Humidity:
5%–95%
RH
Expected
Exception Handling
Result
The white
If the white paper becomes
paper that you
dirty, clean the PDC interior.
use to wipe the
mount panel is
clean.
No metal
If any metal component
component
suffers from severe
rusts.
oxidation, remove the rust
or replace the component in
a timely manner.
If the component is painted,
repaint it after removing the
rust.
8 Maintenance Guide
125