PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)

8.2.1 Monthly Maintenance

Table 8-2 Monthly Maintenance
Maintenance
Item
Three phase
power indicators
Surge protection
module
Liquid crystal
display (LCD)
screen on the
PDC
Connections of
input power
cables and output
power cables
Signs of rodent
movements in the
PDC
Issue 02 (2017-02-24)
Operation
Guide
Check the
luminance of the
indicators.
Check the status
of the surge
protection module
indicator and
circuit breaker.
Touch the LCD
screen with your
finger.
Visual
observation
Visual
observation
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Expected
Exception Handling
Result
The three
Replace the indicator that
phase power
generates no or dim light by
indicators are
referring to
steady on.
Indicator.
The surge
If the indicator of an SPD
protection
module is red, replace the
module
SPD module by referring to
indicator is
8.5.1 Replacing an SPD
green.
Module.
The circuit
If the circuit breaker is
breaker is
switched off, switch it on.
switched
on.
The LCD
Check whether the power cable
screen panel is
is properly connected, and
in good
replace the LCD screen if
condition.
necessary by referring to
Replacing an
The cables
Take measures depending on
are not
the severity.
damaged.
The
terminals
are intact
and secure
and free
from spark
signs and
rust.
There is no
If there is a sign of rodent
sign of rodent
movements, ask a professional
movements in
for advice.
the PDC.
8 Maintenance Guide