Master Programming Level
3.5.3 Relays
PROGRAMMING
1=INPUT ZONES
2=NACS

3=RELAYS

Programming Screen #1
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following screens will appear for each relay to be
programmed:
1=ALARM
2=TROUBLE
3=SUPERVISORY
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The
choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice.
Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
NOTE: A relay programmed with the Silenceable Alarm type will deactivate when the FACP Alarm Silenced LED is illuminated.
3.5.4 System Setup
System Setup allows the programmer to configure the following control panel features:
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and
Waterflow time delay
Banner: This option allows the user to change the top two lines of the LCD display from the factory default readout, which is blank,
to a user defined readout when the control panel is in Normal condition
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time
feature into the FACP memory
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or trouble still exists on the FACP after
the control panel has been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every
two minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at
these rates until the alarm or trouble condition is cleared. If the Trouble Reminder feature is not enabled and a trouble condition is
not cleared within 24 hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the central station if
connected
Canadian Option: This option allows the automatic programming of the FACP to Canadian specifications (refer to "Canadian
Option" on page 70).
Important! For Canadian Applications, this option must be set to ON prior to any other panel programming.
Charger Disable: This option allows the programmer to disable the onboard battery charger in the event an external battery charger
is being used
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2

Timers

SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SFP-5UD & SFP-10UD Series Manual— P/N 52879:C6 6/12/2018
Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three main
circuit board Form-C relays. The following screen will be displayed:
1=RELAY 1
2=RELAY 2
3=RELAY 3
RELAY TYPE
Relay Screen #1
Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following screens to be
displayed:
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing
System Setup Screen #1. The following screen will be displayed:
TIMERS
1=PAS DELAY
2=PRE SIGNAL
3=WATERFLW DELAY
Timer Screen #1
RELAYS
ALARM
TROUBLE
SUPERV
Relays Selection Screen
RELAY TYPE
1=PROCESS MONITOR
2=AC LOSS
3=HAZARD
Relay Screen #2
120
120
0
RELAY TYPE
1=COMM FAIL
2=MEDICAL
3=SILENCEABLE ALARM
Relay Screen #3
SYSTEM SETUP
1=TROUBLE REMIND NO
2=CANADIAN OPTION OFF
3=CHARGR DISABLE
NO
System Setup Screen #2
TIMERS
1=AC LOSS DELAY
2
Timer Screen #2
Programming
67