Power supply
7.4 SITOP PSU8200 13A/36V 3-phase
Order number
Product
Power supply, type
Supplied active power typical
Short-term overload current
Duration of overloading capability for excess cur‐
rent
Constant overload current
Parallel switching for enhanced performance
Numbers of parallel switchable units for en‐
hanced performance
Efficiency
Efficiency at Vout rated, Iout rated, approx.
Power loss at Vout rated, Iout rated, approx.
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
Dynamic load smoothing (Iout: 50/100/50 %),
Uout ± typ.
Load step setting time 50 to 100%, typ.
Load step setting time 100 to 50%, typ.
Dynamic load smoothing (Iout: 10/90/10 %),
Uout ± typ.
Load step setting time 10 to 90%, typ.
Load step setting time 90 to 10%, typ.
Setting time maximum
Protection and monitoring
Output overvoltage protection
Current limitation, typ.
Property of the output Short-circuit proof
Short-circuit protection
Enduring short circuit current RMS value
Overcurrent overload capability in normal oper‐
ation
Overload/short-circuit indicator
Safety
Primary/secondary isolation
Galvanic isolation
Protection class
262
Note
at short-circuit during operation typical
at short-circuit during operation
on short-circuiting during the start-up typical 14 A
typical
6EP3446-8SB10-0AY0
SITOP PSU8200
36 V/13 A
+60 ... +70 °C: Derating 2%/K
468 W
39 A
25 ms
Yes; switchable characteristic
2
94 %
30 W
0.1 %
1 %
0.2 ms
0.2 ms
2 %
0.2 ms
0.2 ms
10 ms
< 48 V
14 A
Yes
Alternatively, constant current characteristic ap‐
prox. 14 A or latching shutdown
14 A
overload capability 150 % Iout rated up to 5 s/min
LED yellow for "overload", LED red for "latching
shutdown"
Yes
Safety extra low output voltage Vout according to
EN 60950-1
Class I
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA