Ac/208 V Ac/210 V Ac Voltage System - Huawei UPS5000-H User Manual

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
6.1.4.2 200 V AC/208 V AC/210 V AC Voltage System
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
When the voltage system is 200 V AC/208 V AC/210 V AC, the power of the entire
system is derated to 50%.
Table 6-6 Recommended power cable cross-sectional areas (100–300 kVA)
Item
Mains
Mains input
input
current (A)
Recomme
nded
cross-
sectional
area
2
(mm
Bypass
Bypass input
input
current (A)
Recomme
nded
cross-
sectional
area
2
(mm
Output
Output current
(A)
Recomme
nded
cross-
sectional
area
2
(mm
Battery
Nominal battery
input
discharge current
(lead-acid
(A)
battery)
Maximum
battery discharge
current (A)
Issue 03 (2021-08-03)
100 kVA
363
L1
2 x 95
L2
2 x 95
L3
2 x 95
N
2 x 95
)
PE
95
289
L1
2 x 95
L2
2 x 95
L3
2 x 95
)
N
2 x 95
PE
95
289
U
2 x 95
V
2 x 95
W
2 x 95
)
N
2 x 95
PE
95
453
542
Copyright © Huawei Technologies Co., Ltd.
150 kVA
200 kVA
544
725
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
150
240
433
577
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
150
240
433
577
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
120
185
679
906
814
1085
6 Installation
250 kVA
300 kVA
906
1088
3 x 185
4 x 185
3 x 185
4 x 185
3 x 185
4 x 185
3 x 185
4 x 185
240
240
722
866
3 x 185
4 x 185
3 x 185
4 x 185
3 x 185
4 x 185
3 x 185
4 x 185
240
240
722
866
3 x 185
4 x 185
3 x 185
4 x 185
3 x 185
4 x 185
3 x 185
4 x 185
240
240
1132
1359
1341
1627
73

Advertisement

Table of Contents
loading

Table of Contents