Huawei UPS5000-H User Manual page 151

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Prerequisites
● A backfeed protection card is installed.
● The backfeed protection card uses relay contact signals and it can connect to
● The backfeed protection card needs to be powered by the UPS output or a
Procedure
Step 1 Connect cables to the backfeed protection card.
Issue 03 (2021-08-03)
NO TICE
any power signal with a voltage of 240 V AC or less and a current of less than
6 A.
more reliable third-party power supply to ensure that the backfeed protection
card can isolate faults if backfeed faults occur during power supply in battery
mode.
If the UPS output power supply is used, select a shunt release that matches
the rated voltage based on the voltage system. (Currently, only the 800 kVA
UPS supports this feature.)
Table 6-11 Shunt release selection
UPS Voltage System
Three-phase four-wire
Three-phase four-wire
Three-phase four-wire
Three-phase four-wire
Copyright © Huawei Technologies Co., Ltd.
UPS Voltage Level
380 V
400 V
415 V
480 V
6 Installation
Supply Voltage to Shunt
Release
220 V
230 V
240 V
230 V