Huawei UPS5000-H User Manual page 209

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Table 11-2 Environmental specifications
Item
Operating temperature
Storage temperature
Humidity
Altitude
Table 11-3 Safety compliance
Safety Certification
CE
CB
TUV
CQC
CCC
TLC
RCM
Table 11-4 EMC
EMC Test Item
Conducted emission
Radiated emission
Low-frequency signal interference
ESD immunity
Conducted susceptibility
Radiated susceptibility
Issue 03 (2021-08-03)
Specifications
0–55°C
Temperature derating coefficient: not derated at 0°C–40°C, derated
to 0.9 at 41°C–45°C, derated to 0.8 at 46°C–50°C, and derated to
0.7 at 51°C–55°C
–40°C to +70°C
0%–95% RH (non-condensing)
0–1000 m
When the altitude is greater than 1000 m, the power is derated as
described in IEC 62040-3. The upper limit of the altitude is 4000 m.
Copyright © Huawei Technologies Co., Ltd.
Standard
EN 62040-1:2013
IEC 62040-1:2013
EN 62040-1:2013
CQC 3108-2011
GB 7260.1-2008
YD/T 2165-2017
IEC 62040-2
Standard
EN/IEC 62040-2
EN/IEC 62040-2
IEC 61000-2-2
IEC 61000-4-2
EN/IEC 62040-2
EN/IEC 61000-4-6
EN/IEC 62040-2
EN/IEC 61000-4-3
11 Technical Specifications
201