Huawei UPS5000-H User Manual page 211

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Item
400 kVA/500 kVA
Voltage
0–30°C: not
range
derated at 323–485
V, derated from
100% load to 45%
load at 323–191 V,
and derated from
45% load to 35%
load at 191–138 V
30–40°C: not
derated at 342–485
V, derated from
100% load to 45%
load at 342–191 V,
and derated from
45% load to 35%
load at 191–138 V
Rated
50 Hz/60 Hz
frequency
Frequency
40–70 Hz
range
Power factor
● > 0.99 (100% load)
● > 0.98 (50% load)
● > 0.94 (30% load)
Harmonic
● THDi < 9% (30% linear load), THDi < 6% (50% linear load), THDi < 3% (100%
current
linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear load), THDi <
5% (100% non-linear load)
Remarks:
1. The preceding specifications are met when the mains input and bypass input
share a power source.
2. The input THDu is less than 2%.
Issue 03 (2021-08-03)
600 kVA
380 V/400 V/415 V:
0–30°C: not derated at
323–485 V, derated
from 100% load to 45%
load at 323–191 V, and
derated from 45% load
to 35% load at 191–138
V
30–40°C: not derated at
342–485 V, derated
from 100% load to 45%
load at 342–191 V, and
derated from 45% load
to 35% load at 191–138
V
200 V/208 V/210 V:
0–30°C: not derated at
170–260 V, derated to
70% load at 170–138 V
30–40°C: not derated at
180–260 V, derated to
70% load at 180–138 V
Copyright © Huawei Technologies Co., Ltd.
11 Technical Specifications
800 kVA
380 V/400 V/415 V:
0–30°C: not derated at 323–485 V,
derated from 100% load to 45%
load at 323–191 V, and derated
from 45% load to 35% load at
191–138 V
30–40°C: not derated at 342–485
V, derated from 100% load to 45%
load at 342–191 V, and derated
from 45% load to 35% load at
191–138 V
480 V:
0–40°C: not derated at 384–528 V,
derated from 100% load to 50%
load at 384–240 V, and derated
from 50% load to 40% load at
240–192 V
203