UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Table 10-1 Troubleshooting
Case
The
rectifier is
abnormal
.
The
inverter is
abnormal
.
The
charger
generates
an alarm.
The UPS
works in
bypass
mode
and does
not
transfer
to
inverter
mode.
The
bypass is
abnormal
.
Issue 03 (2021-08-03)
Symptom
The UPS rectifier
cannot work, and
the bus voltage is
not boosted.
The buzzer buzzes,
the fault indicator is
on, the inverter is
faulty, and the UPS
transfers to bypass
mode.
The buzzer buzzes,
the fault indicator is
on, and the charging
function fails.
When the mains is
normal, the UPS
works in bypass
mode and does not
transfer to inverter
mode.
The buzzer buzzes,
and the fault
indicator is on.
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
The mains voltage
exceeds the upper
threshold 280 V or is
less than the lower
threshold 80 V.
PFC soft-start fails.
The power module is
faulty.
Output overload or
short-circuit exists.
The power module is
faulty.
The charger fails.
The charger
experiences
overcurrent.
The charger
experiences
undervoltage.
The UPS is set to
ECO mode.
The number of
bypass transfer times
reaches the upper
limit.
The bypass thyristor
is damaged.
10 Troubleshooting
Measure
Check whether the
mains voltage is
beyond the allowed
range. If so, contact
the electric power
company.
Replace the power
module.
Replace the power
module.
Reduce the load or
troubleshoot the
short circuit.
Replace the power
module.
Replace the power
module.
Replace the power
module.
Check whether the
configured number
of batteries is
correct. If the
configured number
of batteries is correct
but the alarm
persists, replace the
power module.
Set the working
mode correctly.
On the LCD, choose
Clear Faults.
Replace the bypass
module.
198