UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Table 6-5 Recommended input/output circuit breakers
Compone
Specificat
nt Name
a
ions
(200
kVA)
Mains
400 A/3P
input
circuit
breaker
Bypass
400 A/3P
input
circuit
breaker
Downstre
400 A/3P
am
output
circuit
breaker
a: recommended model when the short-circuit current where the circuit breaker is located is less
than 65 kA
Issue 03 (2021-08-03)
recommended in the table apply only when the following requirements are
met:
Routing mode: The cables are routed over a tray or bracket in a single
layer (E in IEC 60364-5-52). The distance between cables should be
greater than twice the cable diameter. Routing mode: The cables are
routed over a tray or bracket in a single layer (E multi-core and G single-
core in IEC 60364-5-52).
Ambient temperature: 30°C
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%.
Conductor insulation: PVC insulation
The 90°C flexible cables with copper conductors are used.
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
Specificat
Specificat
a
ions
ions
(300
(400
kVA)
kVA)
630 A/3P
800 A/3P
630 A/3P
630 A/3P
630 A/3P
630 A/3P
NO TE
● The input circuit breakers recommended are for reference only.
● If multiple loads are connected, use recommended specifications for branch circuit
breakers.
● The circuit breaker selection principle is to protect loads and cables, and the cascading
principle is to achieve specific protection.
Copyright © Huawei Technologies Co., Ltd.
Specificat
a
a
ions
(500
kVA)
1000
A/3P
800 A/3P
800 A/3P
Specificat
Specificat
a
a
ions
ions
(600
(700
kVA)
kVA)
1250
1600
A/3P
A/3P
1000
1250
A/3P
A/3P
1000
1250
A/3P
A/3P
6 Installation
Specificat
a
ions
(800
kVA)
1600
A/3P
1250
A/3P
1250
A/3P
72