Table 6-5 Recommended input/output circuit breakers
Compone
Specificat
nt Name
a
ions
(200
kVA)
Mains
400 A/3P
input
circuit
breaker
Bypass
400 A/3P
input
circuit
breaker
Downstre
400 A/3P
am
output
circuit
breaker
a: recommended model when the short-circuit current where the circuit breaker is located is less
than 65 kA
Issue 03 (2021-08-03)
recommended in the table apply only when the following requirements are
met:
–
Routing mode: The cables are routed over a tray or bracket in a single
layer (E in IEC 60364-5-52). The distance between cables should be
greater than twice the cable diameter. Routing mode: The cables are
routed over a tray or bracket in a single layer (E multi-core and G single-
core in IEC 60364-5-52).
–
Ambient temperature: 30°C
–
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%.
–
Conductor insulation: PVC insulation
–
The 90°C flexible cables with copper conductors are used.
–
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
Specificat
Specificat
a
ions
ions
(300
(400
kVA)
kVA)
630 A/3P
800 A/3P
630 A/3P
630 A/3P
630 A/3P
630 A/3P
NO TE
● The input circuit breakers recommended are for reference only.
● If multiple loads are connected, use recommended specifications for branch circuit
breakers.
● The circuit breaker selection principle is to protect loads and cables, and the cascading
principle is to achieve specific protection.
Copyright © Huawei Technologies Co., Ltd.
Specificat
a
a
ions
(500
kVA)
1000
A/3P
800 A/3P
800 A/3P
Specificat
Specificat
a
a
ions
ions
(600
(700
kVA)
kVA)
1250
1600
A/3P
A/3P
1000
1250
A/3P
A/3P
1000
1250
A/3P
A/3P
6 Installation
Specificat
a
ions
(800
kVA)
1600
A/3P
1250
A/3P
1250
A/3P
72