Huawei UPS5000-H User Manual page 215

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Item
400 kVA/500 kVA
Transfer time
● Double conversion mode: uninterrupted transfer 0 ms; interrupted transfer ≤
● S-ECO mode: 0 ms
Output voltage
Voltage imbalance: ±1%
imbalance
Phase imbalance: 120±1° (balanced load and unbalanced load)
Inverter
Inverter overload capability for front-to-back airflow:
overload
● 105% < load ≤ 110%: transfers to bypass mode after 60 min or longer
capability
● 100% < load ≤ 110%: transfers to bypass mode after 60 min or longer
● 110% < load ≤ 125%: transfers to bypass mode after 10 minutes or longer
● 125% < load ≤ 150%: transfers to bypass mode after 1 minute or longer
● Load > 150%: The inverter can run for 200 ms or longer and withstand at
Inverter overload capability for top airflow:
● 100% < load ≤ 110%: transfers to bypass mode after 60 minutes or longer
● 110% < load ≤ 125%: transfers to bypass mode after 10 minutes or longer
● 110% < load ≤ 125%: transfers to bypass mode after 1 minute or longer
● 125% < load ≤ 150%: transfers to bypass mode after 1 minute or longer
● 125% < load ≤ 150%: transfers to bypass mode after 20 seconds or more
● Load > 150%: transfers to bypass mode after 200 ms or more; withstands at
Inverter output
If the initial load rate is less than 40%, the inverter output short-circuit can
short-circuit
tolerate twice the rated current for 300 ms.
capability
Bypass
400 kVA: At 40°C,
overload
runs 60 min at 110%
capability
load, 10 min at 125%
load, 1 min at 150%
load, and 100 ms at
over 150% load.
500 kVA: At 25°C,
runs continuously at
125% load; generates
only alarms and
depends on
overtemperature
protection at 150%
load.
Issue 03 (2021-08-03)
5 ms
(ambient temperature ≤ 30°C)
(ambient temperature > 30°C)
least 50 shocks.
(ambient temperature ≤ 30°C)
(ambient temperature > 30°C)
(ambient temperature ≤ 30°C)
(ambient temperature > 30°C)
least 50 shocks
Copyright © Huawei Technologies Co., Ltd.
600 kVA
At 25°C: runs
continuously at
125% load;
generates only
alarms and depends
on overtemperature
protection at 150%
load.
11 Technical Specifications
800 kVA
At 30°C: runs continuously at
135% load; generates only
alarms and depends on
overtemperature protection at
135–150% load.
At 40°C: runs continuously at
125% load; generates only
alarms and depends on
overtemperature protection at
125–150% load.
207