UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
----End
6.10 Connecting a Remote EPO Switch
● Huawei does not provide the EPO switch or cable. Prepare them by yourself.
● Equip the EPO switch with a protective cover to prevent misoperations, and
● Triggering EPO will shut down the rectifier, inverter, charger, and static bypass,
Use a cable to connect the EPO switch to the dry contact port on the control
module of the UPS.
Issue 03 (2021-08-03)
Figure 6-108 Cable connections between the backfeed protection card and
shunt release
(1) Shunt release (provided by the
customer)
NO TICE
The recommended cable size is 0.3 mm
protect the cable with a protective tube.
but will not disconnect the UPS mains input. To power off the UPS completely,
turn off the upstream input switch when you trigger EPO.
Copyright © Huawei Technologies Co., Ltd.
(2) 6 A fuse (prepared by the customer)
2
.
6 Installation
145