Huawei UPS5000-H User Manual page 79

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Item
Battery input
Nominal battery
(lead-acid
discharge current (A)
battery)
Maximum battery
discharge current (A)
Recommend
ed cross-
sectional
area (mm
Battery input
Nominal battery
(SmartLi)
discharge current (A)
Maximum battery
discharge current (A)
Recommended cross-
sectional area
Equipotential
Recommended cross-
ground point
sectional area (mm
Issue 03 (2021-08-03)
PE
+
-
2
)
PE
2
)
NO TE
The rated voltage of the SmartLi is 512 V. The voltage is 408 V at the maximum discharge
current.
The currents listed in the table are measured at a rated voltage of 380 V.
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
When the external conditions such as cable routing or ambient temperature
change, perform verification in accordance with the IEC 60364-5-52 or local
regulations.
For the 400 V rated voltage, multiply the current by 0.95.
For the 415 V rated voltage, multiply the current by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires to 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
The battery cable specifications are selected based on 40 batteries by default
and compatible with application scenarios with 30–50 batteries.
When the mains input and bypass input share a power source, configure
mains input power cables as input power cables. In addition, cables
Copyright © Huawei Technologies Co., Ltd.
600 kVA
700 kVA
240
240
1330
1551
1593
1858
4 x 185
4 x 240
4 x 185
4 x 240
240
240
1247
1454
1564
1825
For details, see the IEC-60364-5-52 specifications and
SmartLi User Manual .
16
6 Installation
800 kVA
240
1773
2123
4 x 240
4 x 240
240
1662
2086
71